首页 >>  正文

s7-200通讯端口被占用

来源:baiyundou.net   日期:2024-09-24

每个S7-200 SMART CPU都提供一个以太网端口和一个RS485端口(端口0),标准型CPU额外支持SB CM01信号板(端口1),信号板可通过STEP 7-Micro/WIN SMART软件组态为RS232通信端口或RS485通信端口。

CPU 通信端口引脚分配

1.S7-200 SMART CPU 集成的 RS485 通信端口(端口0)是与 RS485 兼容的9针 D 型连接器。CPU 集成的 RS485 通信端口的引脚分配如表1. S7-200 SMART CPU 集成 RS485 端口的引脚分配表所示。

表1. S7-200 SMART CPU 集成 RS485 端口的引脚分配

2.标准型 CPU 额外支持 SB CM01 信号板,该信号板可以通过 STEP 7-Micro/WIN SMART 软件组态为 RS485通信端口或者 RS232 通信端口。表 2. 给出了 SB CM01 信号板的引脚分配 。

表2. S7-200 SMART SB CM01 信号板端口(端口1)的引脚分配表

使用STEP 7-Micro/WIN SMART 软件组态 SB CM01 信号板为 RS485通信端口或者RS232通信端口的过程如图 1. SB CM01 信号板组态过程所示。

图1. SB CM01 信号板组态过程

EM DP01通讯端口引脚分配

EM DP01 上的 RS485 串行通信接口是一个 RS485 兼容的九针迷你 D型插口,与欧洲标准 EN 50170 规定的 PROFIBUS标准一致,下图介绍了通讯端口的引脚分配。

图 2. S7-200SMART EM DP01通讯端口的引脚分配

以太网端口连接

S7-200 SMART CPU 的以太网端口有两种网络连接方法:直接连接和网络连接。

直接连接 :

当一个 S7-200 SMART CPU 与一个编程设备、 HMI 或者另外一个 S7-200 SMART CPU 通信时,实现的是直接连接。直接连接不需要使用交换机,使用网线直接连接两个设备即可,如图2.通信设备的直接连接所示。

图 3. 通信设备的直接连接

网络连接 :

当两个以上的通信设备进行通信时,需要使用交换机来实现网络连接。可以使用导轨安装的西门子 CSM1277 4端口交换机来连接多个 CPU 和 HMI 设备,如图 3. 多个通信设备的网络连接所示。

图 4.多个通信设备的网络连接

RS485 网络连接

RS485 网络的传输距离和波特率

RS485 网络为采用屏蔽双绞线电缆的线性总线网络,总线两端需要终端电阻。RS485 网络允许每一个网段的最大通信节点数为 32 个,允许的最大电缆长度则由通信端口是否隔离以及通信波特率大小等两个因素所决定,见表 3. RS485 网段电缆的最大长度所示。

表 3. RS485 网段电缆的最大长度

S7-200 SMART CPU 集成的 RS485 端口以及 SB CM01 信号板都是非隔离型通信端口,允许的最大通信距离为 50m,该距离为网段中第一个通信节点到最后一个节点的距离。如果网络中的通信节点数大于 32 个或者通信距离大于 50m 则需要添加 RS485 中继器拓展网络连接。

注意:

● S7-200 SMART CPU 集成的 RS485 端口以及 SB CM01 信号板都是非隔离型,与网段中其它节点通信时需要做好参考点电位的等电位连接或者使用 RS485 中继器为网络提供隔离。参考点电位不同的节点通信时可能会导致通信错误或者端口烧坏。

● S7-200 SAMRT CPU 与其它节点联网时,可以将 CPU 模块右下角的传感器电源的 M 端与其它节点通信端口的 0V 参考点连接起来做到等电位连接。

RS485 中继器

RS485 中继器可用于延长网络距离,电气隔离不同网段以及增加通信节点数量。中继器的作用如下:

1.延长网络距离:

网络中添加中继器允许将网络再延长 50m ,如果两台中继器连接在一起,中间无其它节点,则可将网络延长 1000m ,一个网络中最多可以使用 9 个西门子中继器。如图 4. 使用 RS485 中继器拓展网络所示。

图 5. 使用 RS485 中继器拓展网络

注意:

S7-200 SMART CPU自由口通信、Modbus RTU通信和USS通信时,不能使用西门子中继器拓展网络。

2.电气隔离不同网段:

隔离网络可以使参考点电位不相同的网段相互隔离,从而确保通信传输质量。

3.增加网络设备:

在一个 RS485 网段中,最多可以连接 32 个通信节点。使用中继器可以向网络中拓展一个网段,可以再连接 32 个通信节点,但是中继器本身也占用一个通信节点位置,所以拓展的网段只能再连接 31 个通信节点。

RS485 网络连接器

西门子提供了两种类型的 RS485 网络连接器(如图 5. RS485网络连接器所示),可使用它们轻松地将多台通信节点连接到通信网络上。一种是标准型网络连接器,另一种则增加了可编程接口。带有可编程接口的网络连接器可以将 S7-200 SMART CPU 集成的 RS485 端口所有通信引脚扩展到编程接口,其中 2 号、7 号引脚对外提供 24VDC电源,可以用于连接 TD400C 。

图 6. RS485网络连接器

网络连接器上两组连接端子,用于连接输入电缆和输出电缆。网络连接器上具有终端和偏置电阻的选择开关,网络两端的通信节点必须将网络连接器的选择开关设置为 On ,网络中间的通信节点需要将选择开关设置为 Off 。典型的网络连接器终端电阻和偏置电阻接线如表 4. 网络连接器终端和偏置电阻所示。

表 4. 网络连接器终端和偏置电阻

使用 SB CM01 信号板可用于连接 RS485 网络,当信号板为终端通信节点时需要接终端电阻和连接偏置电阻,典型的电路图如图 6. SB CM01 信号板终端和偏置电阻接线图所示。

图 7. SB CM01 信号板终端和偏置电阻接线

注意:

● 终端电阻用于消除通信电缆中由于特性阻抗不连续而造成的信号反射。信号传输到网络末端时,如果电缆阻抗很小或者没有阻抗的话,在这个地方就会引起信号反射。消除这种反射的方法,就是在网络的两端端接一个与电缆的特性阻抗相同的终端电阻,使电缆阻抗连续。

● 当网络上没有通信节点发送数据时,网络总线处于空闲状态,增加偏置电阻可使总线上有一个确定的空闲电位,保证了逻辑信号 “0”、“1” 的稳定性。

RS232 连接

RS232 网络为两台设备之间的点对点连接,最大通信距离为15m,通信速率最大为 115.2 Kbit/s 。RS232 连接可用于连接扫描器、打印机、调制解调器等设备。SB CM01 信号板通过组态可以设置为 RS232 通信端口,典型的 RS232 接线方式如图 7. SB CM01 信号板 RS232 连接图所示。

S7-200Smart的多种通讯方式

1.两台S7-200Smart无线通讯

2.组态王/wincc/触摸屏作为主站与S7-200smart从站通讯

3.S7-200Smart作为主站,2个从站分别采集4路模拟量信号和4路开关量信号

4.西门子触摸屏与S7-200SMART以太网无线通讯

5.S7-200 SMART与IO模块之间无线PROFINET通信

6.威纶通触摸屏与S7-200Smart之间无线Ethernet通信


","gnid":"98840cf84cfc3cb57","img_data":[{"flag":2,"img":[{"desc":"","height":"714","title":"","url":"https://p0.ssl.img.360kuai.com/t01dcab175cda711f81.png","width":"960"},{"desc":"","height":"403","title":"","url":"https://p0.ssl.img.360kuai.com/t01aed339b17a0b8013.png","width":"957"},{"desc":"","height":"512","title":"","url":"https://p0.ssl.img.360kuai.com/t01f2b22c9a92456b5d.jpg","width":"696"},{"desc":"","height":"318","title":"","url":"https://p0.ssl.img.360kuai.com/t01004b5218d2eba40f.jpg","width":"473"},{"desc":"","height":"344","title":"","url":"https://p0.ssl.img.360kuai.com/t01f8c208a42112a214.jpg","width":"554"},{"desc":"","height":"176","title":"","url":"https://p0.ssl.img.360kuai.com/t012c69b731c2694540.jpg","width":"408"},{"desc":"","height":"247","title":"","url":"https://p0.ssl.img.360kuai.com/t0105ac3a53327c3f19.jpg","width":"960"},{"desc":"","height":"141","title":"","url":"https://p0.ssl.img.360kuai.com/t01218c3fcdbff6c236.jpg","width":"611"},{"desc":"","height":"166","title":"","url":"https://p0.ssl.img.360kuai.com/t017e8a4ec276968bb3.jpg","width":"436"},{"desc":"","height":"188","title":"","url":"https://p0.ssl.img.360kuai.com/t0143bee9a8a93e0d42.jpg","width":"479"},{"desc":"","height":"162","title":"","url":"https://p0.ssl.img.360kuai.com/t018aa8b76be23175e8.jpg","width":"405"},{"desc":"","height":"165","title":"","url":"https://p0.ssl.img.360kuai.com/t01e2e0daf83acd976d.jpg","width":"384"},{"desc":"","height":"689","title":"","url":"https://p0.ssl.img.360kuai.com/t019c19bf365a768002.png","width":"1024"},{"desc":"","height":"3200","title":"","url":"https://p0.ssl.img.360kuai.com/t01d2b28355e98a0caa.jpg","width":"4267"},{"desc":"","height":"885","title":"","url":"https://p0.ssl.img.360kuai.com/t0159886075e56af5ec.jpg","width":"1181"},{"desc":"","height":"429","title":"","url":"https://p0.ssl.img.360kuai.com/t013850106221f23d2f.png","width":"600"},{"desc":"","height":"423","title":"","url":"https://p0.ssl.img.360kuai.com/t0197c1831dcf1706ff.png","width":"594"},{"desc":"","height":"734","title":"","url":"https://p0.ssl.img.360kuai.com/t0126a5c645c9a7a2aa.png","width":"1024"}]}],"original":0,"pat":"art_src_0,disu_label,fts0,sts0","powerby":"hbase","pub_time":1691981626000,"pure":"","rawurl":"http://zm.news.so.com/b6f87b7111caef33fde733b97797d3fa","redirect":0,"rptid":"ed4b109f67972d5e","rss_ext":[],"s":"t","src":"达泰电子","tag":[{"clk":"kdigital_1:s7","k":"s7","u":""},{"clk":"kdigital_1:cpu","k":"cpu","u":""}],"title":"S7-200 SMART 通信端口以及连接方式

宇章砌1801西门子S7 - 200提示端口无法打开或者另一个程序使用 -
迟夏通15823857873 ______ 在PLC编程软件里点击左下角的《设置PG/PC接口》,弹出的对话框里选择PC/PPI,点确认,然后在左下角里点击通信,双击右上角的刷新,会自动搜索到端口,选择,再确认就可以了

宇章砌1801你好!我有1台S7 - 200 CPU226有2个通讯端口,现已全部在使用,我现在有要与电脑连接监控程序有办法再接吗 -
迟夏通15823857873 ______ 那要看你的这两个通信口都分别用了什么协议了,如果有一个还是默认的PPI,那就可以把这个通信口连接的网络从中取一个点连接到PC接可以了,因为200和PC默认的就是PPI协议,西门子有专用的这种接头即带编程的.

宇章砌1801S7—200有几个通讯口,可扩展吗 -
迟夏通15823857873 ______ 不同的型号通讯口是不一样的!S7-221为一个通讯口,不可扩展通讯接口;S7-222CN为一个通讯口,可扩展一个,共两个;S7-224CN为一个通讯口,可扩展一个,共两个;S7-224XP CN/S7-224XPsi CN为两个通讯口,可扩展两个,共四个;S7-226 CN为两个通讯口,可扩展两个共4个;扩展的模块为EM227

宇章砌1801西门子PLC S7 - 200串口定义成自由口后如何恢复? -
迟夏通15823857873 ______ 如果是S7-200的串口,需要购买适配器或CP5611通信卡,可以用MPI协议.端口是485没错,西门子的串口通信PC/PPI就不要用了,串口通信PC/,很不稳定,2000以上;PPI和现场总线于上位机的通信,一般都是2种. s7-200通讯指令及特...

宇章砌1801各位西门子S7 - 200 PLC通讯为何不能用USB转接口,在不改变计算机接口有什么方法可以解决?
迟夏通15823857873 ______ 可以用USB转232的转接口,然后用西门子的串口编程电缆. 我就正在使用的.出现通讯不正常的情况有2种:1、你的通讯端口设置不一致.需将本地COM口号与PG/PC端口号统一.2、USB口质量不过关,要60左右的那种直连的,不要带延长线的那种. 另外西门子的编程电缆现在都有USB口的.可以直接找代理商购买. 【满意请及时加分,谢谢】

宇章砌1801西门子s7 - 200 两个plc之间建立不了联系
迟夏通15823857873 ______ 1. 硬件设置 例程中的Modbus通讯是在两个S7-200 CPU的0号通讯口间进行的(最好每个CPU都有两个通讯口).在主站侧也可以选择相应库文件 "MBUS_CTRL_P1" 和 "MBUS_MSG_P1"通过1号通讯口通信.通讯口1与Micro/WIN建立...

宇章砌1801能否删除S7 - 200的库存储区中不用的MODBUS占用地址?
迟夏通15823857873 ______ 没有使用Modbus通讯,怎么可能地址又被Modbus占用了呢?是否楼主无意中调用了Modbus通讯功能块了,如果调用了把这一部分程序删除即可.

宇章砌1801西门子CPU 315 2 - DP的两个口都占用了(硬件组态),下载、上传和监控用哪个口?
迟夏通15823857873 ______ CPU 315 2-DP的两个端口均可以用来下载、上传和监控. 一般情况下带电插拔不会损害通讯口,不能连接PLC可能由PC/PG接口设定有误造成的. 以USB PC-ADAPTER为例 当你选择使用MPI端口,需要设定PC/PG接口,将S7-ONLINE的访问点...

宇章砌1801台式电脑可以直接和S7 - 200通讯吗?为什么? -
迟夏通15823857873 ______ 可以的呀,只要您的主板上 带有RS232接口,或者可以另外买一个 板载PCI转RS232 的转接卡就行了,那种USB转RS232 的转接线效果并不好,上次给一家公司配电脑,送过去了之后才被告知还需要RS232接口,然后使用了N多个 USB转RS232 转接线,效果都不好,通信失败的概率很高,后来换了一个 板载PCI转RS232 转接卡,就解决了.

宇章砌1801如何修改S7 - 200中的通讯地址
迟夏通15823857873 ______ 打开200软件左侧的点击系统块有通讯端口0和1你用那个口就把下面的PLC地址改为10然后确定这个时候下载到当前PLC即可